Pump Piping Requirements, How To Be Accurate Please See Here!

In order to prevent the weight of pipelines and valves and the forces and moments generated by the thermal stress of pipelines from exceeding the maximum allowable external loads at the pump inlet and outlet, pipe racks must be installed on the suction and discharge pipelines of the pump.
The maximum allowable load of the pump nozzle should be provided by the pump manufacturer.For pumps with vertical inlet or vertical outlet, in order to reduce the force on the pump nozzle, a pipe rack must be installed above the nozzle, and its plane position should be as close to the nozzle as possible. The longitudinal beam of the pipe gallery can be used to support the pipeline, so the pump is often arranged under the pipe gallery.
In order to improve the suction performance of the pump, the pump suction pipeline should be shortened as much as possible, with as few bends as possible (it is best to use a large curvature radius for the elbow) to reduce pipeline resistance loss.
In order to prevent cavitation of the pump, the pump suction pipeline should avoid the sac-shaped part where gas accumulates as much as possible. If it cannot be avoided, a DN15 or DN20 exhaust valve should be installed at the sac-shaped part.
When the suction pipe of the pump is in a vertical direction, if a reducer is configured on the suction pipe, an eccentric reducer should be configured to avoid the formation of air pockets. When conveying liquids with a density less than 650Kg/m³, such as liquefied petroleum gas and liquid ammonia, the suction pipe of the pump should have a slope of 1/10~1/100 towards the pump, so that the gas generated by vaporization returns to the suction tank to avoid cavitation of the pump.
At the inlet of a single-suction pump, it is best to configure a straight pipe of about 3 times the inlet diameter.
For double-suction pumps, in order to avoid cavitation of bidirectional suction horizontal centrifugal pumps, the double suction pipes should be arranged symmetrically to ensure uniform flow distribution on both sides. Vertical pipes are directly connected through elbows, but the axis of the pump must be perpendicular to the plane where the elbow is located. At this time, the inlet piping is required to be as short as possible, and the elbow is connected to a reducer and then to the inlet flange. Under other conditions, there should be a straight pipe section of not less than 3 times the pipe diameter before the pump inlet.
Drain the shut-off valve and check valve at the pump outlet with a drain valve. When the pipe diameter is greater than DN50, a drain valve can also be opened on the valve cover of the check valve to install a drain valve. The inlet and outlet valves of pumps of the same specification should use the same elevation as much as possible.
The weight of the valves on the inlet and outlet pipelines of non-metallic pumps must not be pressed on the pump body. A pipe rack should be set to prevent the pump body from being crushed and the pipelines before and after the valve from being twisted when the valve is opened and closed. The exhaust pipe of the steam reciprocating pump should have fewer bends, and a discharge pipe should be installed at the location where condensate may accumulate. A muffler should also be installed if the discharge volume is large. The steam inlet pipe should be equipped with a condensate discharge pipe before the steam inlet valve to prevent water from hitting the cylinder.
The steam reciprocating pump generally has a large vibration during operation, and the pipeline connected to the pump should be well fixed.
When the distance between the center line of the pump outlet and the center line of the corridor column is greater than 0.6m, the swing check valve on the outlet pipeline should be placed in a horizontal position, and it is not allowed to install a net valve on the valve cover.
When the pipeline is mounted above the pump and the motor, the pipeline must be of sufficient height so as not to affect the lifting of the lifting equipment. Pipelines that transport corrosive liquids should not be arranged above the prime mover.
The net distance from the bottom of the pipeline in the lower part of the corridor to the floor should not be less than 4m to meet the maintenance requirements. When the pipeline is mounted above the pump body, the clearance height between the bottom of the pipe and the ground should be no less than 2.2m.